{"product_id":"ng-blu-multi-zone-24k-wall-mount-air-handler","title":"NG BLU+ Multi-Zone 24,000 BTU Wall-Mount Air Handler - 23.5 SEER2 (MIBMHW24D)","description":"\u003cp\u003eThe largest wall-mounted head in the multi-zone range at two tons, with 2.7 L\/h of moisture removal, the most of any BLU+ indoor unit. Before specifying it, check the port sizing on your condenser: this head uses a 3\/8 in. liquid and 5\/8 in. gas connection, which is larger than every other multi-zone head in the line and larger than the standard multi-zone port. Confirm compatibility and any required adapters with NG before ordering.\u003c\/p\u003e\u003ch3\u003eSpecifications\u003c\/h3\u003e\u003ctable\u003e\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNominal cooling capacity\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e24,000 BTU\/h (9,700 - 27,000 BTU\/h)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNominal heating capacity\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e25,000 BTU\/h (11,300 - 32,700 BTU\/h)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSEER2 \/ EER2\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e23.5 \/ 13.0\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eHSPF2 (Region IV \/ Region V)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e10.0 \/ 7.7\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCOP\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3.08\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eHeating at 17°F\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e21,300 BTU\/h\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eHeating at 5°F\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e17,800 BTU\/h\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eHeating at -4°F\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e12,300 BTU\/h\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eHeating at -13°F\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e11,000 BTU\/h\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMoisture removal\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e2.7 L\/h\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eAirflow (Turbo\/Hi\/Mi\/Lo)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e759.3 \/ 588.6 \/ 459.1 \/ 382.6 CFM\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSound level\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e54.0 \/ 48.5 \/ 43.5 \/ 27.5 \/ 20.5 dB(A)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePower supply\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e208\/230V \/ 60Hz \/ 1Ph\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMCA \/ max fuse\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3.0A \/ 15A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eFan motor RLA\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1.3A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMetering\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eEXV plus throttle valve\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eLine set\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3\/8 in. liquid, 5\/8 in. gas\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMax line length \/ height difference\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e164 ft \/ 82 ft\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDimensions (W x D x H)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e42.60 x 9.21 x 13.27 in.\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNet \/ gross weight\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e30.86 \/ 40.56 lb\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eIndoor operating range\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e60 - 90°F cooling, 32 - 86°F heating\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\u003c\/table\u003e\u003ch3\u003eMulti-zone component, sold separately\u003c\/h3\u003e\u003cp\u003eThis is an indoor component of a BLU+ multi-zone system and does not operate on its own. It must be paired with a BLU+ multi-zone condenser (MOBMH180D, MOBMH270D, MOBMH360D or MOBMH480D). Confirm total connected capacity and port sizing against the condenser before ordering.\u003c\/p\u003e\u003ch3\u003eInstallation and compliance\u003c\/h3\u003e\u003cp\u003eR-454B and R-32 are A2L refrigerants, classified as mildly flammable. Installation, charging and service must be performed by a licensed HVAC contractor holding EPA Section 608 certification and trained on A2L handling. Local code may require leak detection, minimum room volume per pound of charge, or specific line set materials. Verify requirements before quoting.\u003c\/p\u003e\u003cp\u003e\u003cem\u003eSpecifications are taken from the manufacturer's published data sheet and are subject to change without notice. Confirm capacity, electrical requirements and refrigerant charge against the documentation shipped with the unit before installation.\u003c\/em\u003e\u003c\/p\u003e","brand":"NG Trade","offers":[{"title":"Default Title","offer_id":45804164841581,"sku":"MIBMHW24D","price":748.12,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0637\/2419\/1853\/files\/ng-wall-head-front_cbb0894c-cc9f-4338-a721-b3043eb05775.png?v=1788874767","url":"https:\/\/willardshvacsupply.com\/products\/ng-blu-multi-zone-24k-wall-mount-air-handler","provider":"Willard's HVAC Supply","version":"1.0","type":"link"}