{"product_id":"ng-saja-multi-zone-18k-condenser-2-zone-r32","title":"NG SAJA Multi-Zone 17,700 BTU Inverter Condenser - 2 Zone, 22 SEER2, R-32 (MOSA32181)","description":"\u003cp\u003eA two-zone R-32 condenser at 22 SEER2, and the least expensive way into a multi-zone system in the NG range. It pairs with any two SAJA indoor units in the published combinations, so a 7K bedroom head and a 12K living room head can run on their own schedules from one outdoor unit. Rated to -13°F ambient in heating, with 14,500 BTU\/h still available at 5°F. Comes pre-charged for 49.2 ft of line; longer runs need 0.16 oz per additional foot. Indoor units sold separately.\u003c\/p\u003e\u003ch3\u003eSpecifications\u003c\/h3\u003e\u003ctable\u003e\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSystem format\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1 drive 2 - up to 2 indoor units\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCooling capacity at 95°F\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e17,700 BTU\/h (3,800 - 19,800 BTU\/h range)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eHeating capacity at 47°F\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e18,000 BTU\/h (4,200 - 22,000 BTU\/h range)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eHeating at 17°F\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e14,700 BTU\/h\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eHeating at 5°F\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e14,500 BTU\/h\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSEER2 \/ EER2\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e22 \/ 12.3\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eHSPF2 (Region IV \/ Region V)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e10 \/ 8\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCOP\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3.8\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePower supply\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e208-230V, 60Hz, 1Ph\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCooling \/ heating power input\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1,440W \/ 1,390W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated current (cooling \/ heating)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e6.39A \/ 6.17A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMax input current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e13A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMCA\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e15A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRecommended fuse \/ MOP\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e20A \/ 20A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMax power\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e2.7 kW\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCompressor\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eGMCC rotary, 4,345W, 10-120 Hz, VG74 \/ 420ml oil\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eAirflow\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1,529 CFM (2,600 m3\/h)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSound pressure \/ sound power\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e54 dB(A) \/ 64 dB(A)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRefrigerant\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eR-32, 1.1 kg \/ 38.8 oz charged volume\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eAdditional charge\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e15 g\/m (0.16 oz\/ft) beyond the 49.2 ft pre-charge\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePort connections\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1\/4 in. liquid, 3\/8 in. gas\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMax total pipe length\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e131 ft (40 m)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMax length to one indoor unit\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e82 ft (25 m)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMax height difference (IDU to ODU)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e49 ft (15 m)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMax height difference between IDUs\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e33 ft (10 m)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDimensions (W x D x H)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e34.65 x 13.90 x 21.93 in.\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNet \/ gross weight\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e75.0 \/ 80.5 lb\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePower wiring (ODU)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3 x 14 AWG\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInterconnect wiring\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e4 x 18 AWG\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eAmbient range\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e-13 - 125°F cooling, -13 - 75°F heating\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eValid indoor combinations\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e7+7, 7+9, 7+12, 7+18, 9+9, 9+12, 9+18, 12+12\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\u003c\/table\u003e\u003ch3\u003eBuilding the system\u003c\/h3\u003e\u003cp\u003ePair with SAJA indoor units, ordered separately: 7K, 9K, 12K and 18K wall-mount heads (MISAW3207 \/ 3209 \/ 3212 \/ 3218) and the 12K 8-way cassette (MISAC3212). Permitted combinations are fixed by the manufacturer's chart, not by simple capacity addition.\u003c\/p\u003e\u003ch3\u003eInstallation and compliance\u003c\/h3\u003e\u003cp\u003eR-454B and R-32 are A2L refrigerants, classified as mildly flammable. Installation, charging and service must be performed by a licensed HVAC contractor holding EPA Section 608 certification and trained on A2L handling. Local code may require leak detection, minimum room volume per pound of charge, or specific line set materials. Verify requirements before quoting.\u003c\/p\u003e\u003cp\u003e\u003cem\u003eSpecifications are taken from the manufacturer's published data sheet and are subject to change without notice. Confirm capacity, electrical requirements and refrigerant charge against the documentation shipped with the unit before installation.\u003c\/em\u003e\u003c\/p\u003e","brand":"NG Trade","offers":[{"title":"Default Title","offer_id":45804183257197,"sku":"MOSA32181","price":1412.7,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0637\/2419\/1853\/files\/ng-saja-condenser-studio_7d25358c-9b6c-4701-921f-c6b5436e66ee.png?v=1788874884","url":"https:\/\/willardshvacsupply.com\/products\/ng-saja-multi-zone-18k-condenser-2-zone-r32","provider":"Willard's HVAC Supply","version":"1.0","type":"link"}