{"product_id":"ng-saja-multi-zone-30k-condenser-4-zone-r32","title":"NG SAJA Multi-Zone 30,000 BTU Inverter Condenser - 4 Zone, 23 SEER2, R-32 (MOSA32301)","description":"\u003cp\u003eA four-zone R-32 condenser at 23 SEER2, and the best low-temperature performer in the SAJA multi-zone range as a share of nameplate: 27,200 BTU\/h at 17°F against 30,000 BTU\/h nominal. It ships pre-charged for 98.4 ft of line and allows 263 ft total across the system, which covers most whole-house retrofits without field charging beyond the additional-length allowance. Two, three or four indoor units per the published combination chart. Indoor units sold separately.\u003c\/p\u003e\u003ch3\u003eSpecifications\u003c\/h3\u003e\u003ctable\u003e\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSystem format\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1 drive 4 - up to 4 indoor units\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCooling capacity at 95°F\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e30,000 BTU\/h (6,000 - 38,200 BTU\/h range)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eHeating capacity at 47°F\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e30,000 BTU\/h (6,300 - 36,000 BTU\/h range)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eHeating at 17°F\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e27,200 BTU\/h\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eHeating at 5°F\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e24,600 BTU\/h\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSEER2 \/ EER2\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e23 \/ 12.5\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eHSPF2 (Region IV \/ Region V)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e10 \/ 8.5\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCOP\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3.9\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePower supply\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e208-230V, 60Hz, 1Ph\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCooling \/ heating power input\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e2,400W \/ 2,250W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated current (cooling \/ heating)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e10.65A \/ 9.98A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMax input current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e23A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMCA\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e26A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRecommended fuse \/ MOP\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e30A \/ 40A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMax power\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e4.6 kW\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCompressor\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eGMCC rotary, 7,640W, 12-120 Hz, VG74 \/ 620ml oil\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eAirflow\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e2,353 CFM (4,000 m3\/h)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSound pressure \/ sound power\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e58 dB(A) \/ 68 dB(A)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRefrigerant\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eR-32, 1.9 kg \/ 67.0 oz charged volume\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eAdditional charge\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e15 g\/m (0.16 oz\/ft) beyond the 98.4 ft pre-charge\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePort connections\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1\/4 in. liquid, 3\/8 in. gas\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMax total pipe length\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e263 ft (80 m)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMax length to one indoor unit\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e115 ft (35 m)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMax height difference (IDU to ODU)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e49 ft (15 m)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMax height difference between IDUs\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e33 ft (10 m)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDimensions (W x D x H)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e41.18 x 17.91 x 31.81 in.\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNet \/ gross weight\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e148.8 \/ 157.6 lb\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePower wiring (ODU)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3 x 10 AWG\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInterconnect wiring\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e4 x 18 AWG\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eAmbient range\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e-13 - 125°F cooling, -13 - 75°F heating\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eValid indoor combinations\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eTwo, three or four heads; e.g. 9+18, 7+9+12, 9+9+12, 7+7+9+12, 9+9+12+12\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\u003c\/table\u003e\u003ch3\u003eBuilding the system\u003c\/h3\u003e\u003cp\u003ePair with SAJA indoor units, ordered separately: 7K, 9K, 12K and 18K wall-mount heads (MISAW3207 \/ 3209 \/ 3212 \/ 3218) and the 12K 8-way cassette (MISAC3212). Permitted combinations are fixed by the manufacturer's chart, not by simple capacity addition.\u003c\/p\u003e\u003ch3\u003eInstallation and compliance\u003c\/h3\u003e\u003cp\u003eR-454B and R-32 are A2L refrigerants, classified as mildly flammable. Installation, charging and service must be performed by a licensed HVAC contractor holding EPA Section 608 certification and trained on A2L handling. Local code may require leak detection, minimum room volume per pound of charge, or specific line set materials. Verify requirements before quoting.\u003c\/p\u003e\u003cp\u003e\u003cem\u003eSpecifications are taken from the manufacturer's published data sheet and are subject to change without notice. Confirm capacity, electrical requirements and refrigerant charge against the documentation shipped with the unit before installation.\u003c\/em\u003e\u003c\/p\u003e","brand":"NG Trade","offers":[{"title":"Default Title","offer_id":45804183683181,"sku":"MOSA32301","price":2307.85,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0637\/2419\/1853\/files\/ng-saja-condenser-studio_c76b1297-c98b-4a71-b2c0-4d1b95fed30c.png?v=1788874890","url":"https:\/\/willardshvacsupply.com\/products\/ng-saja-multi-zone-30k-condenser-4-zone-r32","provider":"Willard's HVAC Supply","version":"1.0","type":"link"}